DOCUMENTATION:
1. FRAMO MOUNTING INSTRUCTION: GENERAL RECOMMENDATIONS AND REQUIREMENTS FOR DESIGN,
HANLING AND INSTALLATION OF THE FRAMO CARGO PUMPING SYSTEM
2. FRAMO DRAWING PUMPING SYSTEM: GENERAL ARRANGEMENT FRAMO SPECIFICATION, EQUIPMENT
DRAWING, TECHNICAL DATA, SYSTEM DRAWINGS
3. FRAMO DRAWING PIPING SYSTEM: PIPING SPECIFICATION, LATOUT DRAWINGS, COMPONENT
DRAWINGS.
4. FRAMO SERVICE MANUAL PUMPING SYSTEM:
TECHNICAL DATA, INITIAL START UP,OPERATION, MAINTENANCE ,DRAWING – PART LISTS.
5. FRAMO SERVICE MANUAL PIPING SYSTEM: PIPING SPECIFICATION, LAYOUT DRAWINGS.
1.
THE FRAMO HYDRAULIC SYSTEM IS DESIGNED AS A CENTRAL HYDRAULIC RING LINE SYSTEM.
THE HYDRAULIC POWER UNIT DELIVERS OIL TO THE MAIN PRESSURE LINE, AND FROM THIS
LINE IT IS POSSIBLE TO RUN A NUMBER OF HYDRAULIC MOTORS AS LONG AS THE OIL
DELIVERY IS SUFFICENT. IN ORDER TO CONTROL THE SPEED OF THE MOTOR AND TO
PREVENT OVER-SPEED, A CONTROL VALVE IS FITTED FOR EACH MOTOR.
THE HYDRAULIC SYSTEM IS BUILT
AS A CENTRAL HYDRAULIC MAIN RING LINE SYSTEM IN OPEN LOOP WHERE HYDRAULIC PUMPS
DELIVER OIL TO A MAIN PRESSURE LINE
HYDRAULIC POWER UNIT
HYDRAULIC OIL STORAGE / CLEAN
OIL DRAIN TANK
HYDRAULIC OIL TRANSFER UNIT
TANK CLEANING PUMP
SUBMERGED BALLAST PUMP
PORTABLE PUMP
WINCH FOR PORTABLE PUMP
HEAT EXCHANGER
SUBMERGED CARGO PUMP
THRUSTER MOTOR
HYDRAULIC SYSTEM CONTROL
PANEL
REMOTE CONTROL ASSEMBLY
THE FRAMO CARGO PUMPING
SYSTEM IS CONTROLLED BY A PROGRAMMABLE LOGIC CONTROL ( PLC ) INSTALLED INSIDE THE CONTROL
PANEL. THE PLC IS PROGRAMMED BY FRAMO AND PROVIDES THE LOGIC FOR SAFE OPERATION
OF THE SYSTEM. MODIFICATIONS OF THE SYS./ PROGRAM CARRIED OUT BY OTHER MAY
EFFECT THE WARRANTY OF HT SYSTEM.
2. WATER CONTENT: MAX.
RECOMMENDED WATER CONTENT IS 300 PPM ( 0.03 % ) ,AND MUST UNDER NO CIRCUMTANCES
BE ABOVE 500 PPM ( 0.05 % ).IF IN DOUBT, PLEASE CONTACT FRAMO.
3. CLEANLESS LEVEL: THE REQUIRED CLEANLINESS LEVEL IS BASED UPON ISO SOLID
CONTAMINANT CODE ISO 4406.
CODE : NUMBER OF PARTICLES: PARTICLE SIZE ACC. TO 1999 REVISION
16 / 12 320 / 640 6
MICRON ( C )
20 / 40
14 MICRON ( C )
15 / 11 160 / 320 6 MICRON ( C )
10 / 20
14 MICRON ( C )
RECOMMENDED CLEANLINESS LEVEL
IS CODE 16 / 12 ACCORDING TO ISO 4406 ( OR CETOP PR 20).16 / 12 MEANS THAT
NUMBER OF PARTICLES: ABOVE 6 MICRON IN 100 ML IS BETWEEN 32000 AND 64000. ABOVE
14 MICRON IN 100 ML IS BETWEEN 2000 AND 4000
2. SUBMERGED CARGO PUMPS: SUBMERGED CARGO PUMPS SHOULD BE INSTALLED AT THE AFT
END OR IN THE LOWEST PART OF EACH TANK, LOCATED EITHER TO PORT OR STARBOARD
LOCAL CONTROL V. / STRIPPING V./ CARGO V. / COFFERDAM
PURGING CONNECTION
CARGO PIPE PURGING CONNECTION / EXHAUST TRAP DRAIN V.
/ HYDRAULIC PRESSURE SERVICE V.
3. SUBMERGED BALLAST PUMP
4. FRAMO CONTROL SYSTEM
THE FRAMO CARGO PUMPING
SYSTEM IS NORMALLY OPERATED / MONITORED FROM THE FRAMO CONTROL PANEL,
CONSISTING OF HYDRAULIC SYSTEM CONTROL PANEL AND CARGO PUMP CONTROL PANEL.
EMERGENCY STOP ARRANGEMENT
FRAMO SUPPLIES THREE
EMERGENCY STOP BUTTONA AS STANDART.
HYDRAULIC POWER UNIT
3 POWER PACKS: EACH POWER
PACK CONSIST OF A HYDRAULIC PUMP WITH INTEGRATED PULSATION DAMPER, DRIVEN BY AN
ELECTRIC MOTOR.
JOCKEY PUMP
HYDRAULIC SYSTEM TANK
MAIN HYDRAULIC OIL FILTER
HYDRAULIC OIL COOLER :
THE HYDRAULIC OIL IS COOLED
BY SEA WATER ( FRESH WATER ), AUTOMATICALLY CONTROLLED BY AN ELECTRICALLY
OPERATED ON-OF VALVE .THE VALVE IS OPERATED FROM THE FRAMO PLC ( PROGRAMMABLE
LOGIC KONTROL )TOO LOW WATER FLOW THROUGH THE COOLER MAY CAUSE CORROSION /
FOULING PROBLEMS. TOO HIGH FLOW MAY CAUSE EROSION PROBLEMS
JOCKEY PUMP
THE JOCKEY PUMP SHALL ALWAYS BE RUNNING. THE FOLLOWING WILL BE INDICATED ON THE CONTROL
PANEL IF THE JOCKEY PUMP STOPS WHEN A
POWER PACK IS RUNNING:
THE PROTECTION PRESSURE LOW
ALARM WILL BE INDICATED AND THE JOCKEY PUMP RUNNING LIGHT WILL START
FLASHING.TO RESET THE ALARM ,THE JOCKEY PUMP STOP PUSH BUTTON MUST BE OPERATED.
MAIN POWER PACKS
THE POWER PACKS CAN BE
STARTED IN ANY SEQUENCE. MAX. 4 STARTS SHUOLD BE MADE DURING ONE HOUR. MAX. 2 FOLLOWING STARTS CAN BE MADE, THEN 15
MINUTES BETWEEN EACH. THE STARTS ARE CONTROLLED BY THR PLC, INCLUDING EVENTUAL
STARTS FROM THE LOCAL STARTER CABINET.THE HYDRAULIC PUMP WILL BE DISENGAGED FOR
10 SECONDS DURING THE START-UP.THE LIMIT SWITCHES ON THE SUCTION LINE FOR EACH
POWER PACK WILL STOP OR PREVENT START OF THE CORRESPONDING POWER PACK ONLY . AN
ALARM LIGHT IS PROVIDED FOR EACH POWER PACK TO INDICATED CLOSED VALVE.THE POWER
PACKS WILL AUTOMATICALLY BE RELOADED IN SEQUENCE WHEN THE HYDRAULIC OIL
TEMPERATURE HAS DEGREASED BELOW 60 DEGREES C.
COOLING WATER VALVE
THE VALVE IS AUTOMATICALLY
CONTROLLED AND WILL RECEIVE ‘ OPEN ‘ COMMAND AT HYDRAULIC OILTEMPERATURE ABOVE
50 DEGREES C, IT WIL STAY OPEN UNTIL THE TEMPERATURE DECREASES TO BELOW 30
DEGREES C WHEN ‘CLOSE’ COMMAND IS GIVEN.
THE ‘ FLUSHING MODE ‘ PROGRAM
MAKES IT POSSIBLE TO INCREASE THE OIL TEMPERATURE DURING FLUSHING.
IN THIS MODE THE VALVE IS
CLOSED BELOW 50 DEGREES C AND OPENED AT 58 DEGREES C
ALARM SYSTEM
- ALARMS AND SHUT DOWN OF THE HYDRAULIC SYSTEM.
- ALARMS FOR INDICATION ( PREWARNING ) ONLY.
MAIN ELECTRIC HYDRAULIC POWER
PACK: 3 PCS
JOCKEY PP: 1 PC./ HYDRAULIC
OIL COOLER: 1 PC./ HYDRAULIC OIL TRANSFER UNIT: 1 PC
CARGO PPS: 12 PCS.( TYPE
SD150-SDA-HH107-B333-5 / 335 M3 / H ) /CARGO PPS: 2 PCS. ( TYPE
SD100-5DA-HH23-A210-S )
PORTABLE PUMP: 1 PC ( TYPE :
TK80-DU-HH16-A168-S ) / BALLAST PUMP: 2 PCS. ( TYPE: SB200-2MU-HH90-A372-S )
BOW THRUSTER MOTOR : 1PC. (
600 KW ) / CARGO HEATER : 12 PCS.CAP. 250 KW.
PRESSURE TRANSMITTERS / PRESSURE
SWITCHES / TEMPERATURE TRANSMITTERS
TEMPERATURE SWITCHES / LEVEL
TRANSMITTER
EMERGENCY OVERRIDE PANEL
FOR SYSTEMS WITH BALLAST
PUMPS ( HIGH AVAILABILITY REQUIREMENT ), AN EMERGENCY OVERRIDE PANELIS PROVIDED
BY FRAMO
THRUSTER MOTOR AND CONTROL VALVE
THRUSTER MOTOR
THRUSTER CONTROL VALVE : THE
DSTC ( DIRECTIONAL SPEED TORQUE CONTROLLER ) REGULATES THE TORQUE ( SPEED FROM
ZERO TO MAXIMUM ) OF A FIXED PROPELLER IN BOTH DIRECTIONS ( PORT AND STARBOARD
)
THRUSTER PILOT CONTROL
ASSSEMBLY
BRIDGE AND WINGS PANELS
PROGRAMMABLE LOGIC CONTROL
SPEED SENSOR
COUPLING REQUIREMENT: THE
COUPLING BETWEEN THE HYDRAULIC MOTOR AND THE THRUSTER MUST BE BALANCED IN
ACCORDANCE WITH ISO-1940/1 CLASS G6,3 AT MAXIMUM SPEED.
PERIODICAL MAINTENANCE
FILTER REPLACEMENT:
WHEN THE DIFFERENTIAL
PRESSURE IS HIGH
HYDRAULIC OIL COOLER
INSPECT ANODES AT EVERY 3
MONHTS
CLEAN THE COOLER BUNDLE TUBES
EVERY 6 MONTHS OR IF HEAT EXCHANGE RATE IS TOO LOW.
ANODES : ( BALLAST PUMP AND OTHER PUMPS )
INSPECT THE ANODES ANNUALY
STAINLESS STEEL ON DECK
CLEAN THE STAINLESS STEEL
SURFACES REGULARLY
CARGO HEATERS
CLEAN THE HEATERS ACCORDING
TO SERVICE MANUAL, IF HEAT EXCHANGE RATE IS TOO LOW.
OIL TESTING
ANALYSE THE OIL ( WITH MAX. 4
MONTHS INTERVALS
OIL LEVEL
CHECK THE OIL LEVEL DAILY. (
HIGH LEVEL WHEN POWER PACK ARE STOPS / LOW LEVEL WHEN THEY ARE RUNNING. )
NOISE FROM PUMP / MOTOR
CHECK THE NOISE DAILY WHEN IN
OPERATION
PURGING OF CARGO PUMPS
PURGING OF CARGO PUMPS TO BE
DONE IN ACCORDANCE WITH SEPERATE PURGING INSTRUCTION.
CARGO PUMP TEST
APPLY THE SPECIAL PROCEDURE
IF THE CAPACITY IS GETTING LESS THAN NORMAL
HYDRAULIC OIL LEAKAGE INSPECTION: CHECK IT DAILY WHEN IN OPERATION
DEBRIS SWITCHES AND DETECTORS: DEBRIS SWITCHES TO BE CHECKED EVERY 6 MONTHS OR IF
ALARM IS INDICATED.DEBRIS DETECTORS ( IF INSTALLED ) TO BE CHECKED EVERY 3
MONTHS.
ALARM CHECK
FOLLOWING ALARMS TO BE CHECKED ACCORDING TO
THE SYSTEM MAINTENANCE PROCEDURE AT
EVERY 6 MONTHS
OIL LEVEL ALARM HIGH / OIL
LEVEL ALARM LOW / WEAR ALARM / OIL TEMPERATURE HIGH ALARM
DIRTY FILTER ALARM ( CLOSED
SYSTEM ) / LOCAL SUCTION VALVES / SYSTEM
PRESSURE LOW
OIL LEVEL ALARM LOW LOW / FEED
PRESSURE LOW ( CLOSED SYSTEM )
RETURN LINE VALVES / EMERGENCY
STOP SWITCHES
INSTRUMENT SET-POINT ADJUSTMENT: FOLLOWING INSTRUMENTS TO BE READJUST EVERY 6 MONTH
ACCORDING TO THE INSTRUCTION NO. 1400 – 0180 – 4
PRESURE TRANSMITTER FOR
SYSTEM PRESSURE
TEMPERATURE TRANSMITTER FOR
HYDRAULIC OIL TEMPERATURE
OIL LEVEL TRANSMITTER FOR
HYDRAULIC OIL LEVEL MONITORING.
ELECTRIC MOTORS
THE INSULATION RESISTANCE
MUST BE CHECKED EVERY 6 MONTHS.USE A 500 VDC MEGGER.
IF AN INSULATION RESISTANCE
LOWER THAN 10 MEGAOHMS IS MEASURED BETWEEN FHASES AND TO EARTH, THE WINDING
MUST BE DRIED OUT UNTIL AN ACCEPTABLE READING IS OBTAINED.
LUBRICATE THE BEARINGS EVERY
2500 HOURS
RENEW THE GREASE OF THE
BEARING OR REPLACE THE BERING AFTER 5 YEARS.
ANODES: INSPECT THE ANODES ANNUALLY
ALARM, WEAR INDICATION : CONTACS IN A DEBRIS SWITCH GIVES ALARM ‘ WEAR
INDICATION ‘. THIS MEAN THAT THE DRAIN LINE TO TANK IS CONTAMINATEDBY MAGNETIC
PARTICLES.
ALARM, CONTAMINATED MAIN RETURN FILTER:IT MEANS THAT THE FILTER ELEMENT MUST BE REPLACED.
HIGH CONTAMINATION LEVEL IN OIL.( IF RESULTS
FROM TESTING ....): CHECK MAIN RETURN
FILTER ELEMENT AND ITS BY-PASS VALVES.CONTACT ONE OF FRAMO SERVICE STATION.
ANODES :
THE ANODES INCLUDED BY FRAMO
ARE ONLY INTENDED FOR PROTECTION OF THE PUMP, NOT THE TANK.
CALCULATION OF ANODE LIFETIME
IS BASED ON:
--- 100 % EXPOSURE IN
SEAWATER
--- CURRENT DENSITY WHEN
EXPOSED IN SEAWATER: 0,1 A / M2
--- ZINC ANODE
ELECTROCHEMICAL CAPACITY: 780 AH /KG
IT IS RECOMMENDED TO INSPECT
THE ANODES ANNUALLY UNTIL RATE OF CONSUMPTION IS ESTABLISHED. FURTHER
INSPECTION INTERVALS TO BE BASED ON EXPERIENCE
CALCULATED ANODE LIFETIME FOR BALLAST PUMP
SB200. 12000 HRS
PURGING INTERVALS,-LOGGING OF PURGING RESULT
LOADING VOYAGE DISCHARGE
1. SHORTLY BEFORE 1. 1-2 DAYS AFTERM LOADING 1. SHORTLY BEFORE
LOADING. 2. IF NO LEAKAGE
AT STEP 1, DISCHARGING
PURGE
EVERY FORTNIGHT 2.SHOTLY AFTER
3. IF LEAKAGE IS
DETECTED AT STEP 1, DISCHARGING
OR
AT A LATER STAGE DURING THE VOYAGE,
PURGE THIS PUMP EVERY DAY.
4. IF PUMPS ARE USED FOR CARGO CIRCULATION
DURING THE VOYAGE, THE COFFERDAM MUST BE PURGED
BEFORE AND AFTER STOP
THE PURGING FORM SHOULD BE FILLED IN WITH
THE RESULTS EVERY PURGING OPERATION.
EVALUATION OF THE PURGING RESULTS
CARGO LEAKAGE:
A SMALL LEAKAGE RATE OF UP TO
ABOUT 0.5 LT / DAY ( AND HIGHER WITH LIGHT CARGOES ) DURING PUMP OPERATION IS NORMAL.
CARGO LEAKAGE TO COFFERDAM
NORMALLY INDICATES SHAFT SEAL LEAKAGE.
HYDRAULIC OIL LEAKAGE:
HYDRAULIC OIL IN THE
COFFERDAM NORMALLY INDICATES SHAFT SEAL LEAKAGE, BUT MIGHT COME FROM FLANGE
FACE SEALS IN PIPE STACK / PUMP HEAD OR DAMAGE IN THE PIPE STACK / PUMP HEAD. ( LEAKAGE: 0,25 LT / DAY DURING
PP OPERATION IS NORMAL.
THE MOST IMPORTANT CHECK IS
THE PURGING THE CARGO PUMP’S COFFERDAM.
THIS IS THE ONLY WAY TO CHECK THE SEALING ARRANGEMENT ON THE SUBMERGED PUMPS,
AND RENEWAL OF SEALS SHOULD ONLY TAKE PLACE WHEN THE PURGING ROUTINEIS SHOWING,
AN UNACCEPTABLE LEAKAGE,AND PRESSURE TESTING OR THE COFFERDAM IS INDICATING
WHERE THE PUMPING IS LEAKAGE.IF THE LEAKAGE IS MORE THAN APPROXIMATELY 2-3
LITERS PER 24 HOURS, THE LEAKAGE MUST BE FOUND AND REPAIRED AS SOON AS
POSSIBLE. A LEAKAGE THAT IS NOT BLOWN OUT OF THE COFFERDAM COULD COAGULATE AND BLOCK
THE COFFERDAM .IF A BLOCKAGE OCCURS, THE PORTABLE PUMP MUST BE USED TO EMTY THE
TANK,AND THE CARGO PUMP MUST BE REPAIRED IMMEDIATELY.
A CARGO PUMP WITH A BLOCKED COFFERDAM MUST
NOT BE USED!
OIL SAMPLE
A HYDRAULIC OIL SAMPLE FOR
PARTICLE COUNTING ACCORDING TO ISO 4406 SHOULD BE DRAWN FROM THE VALVE MARKED ‘FRAMO OIL SAMPLE
POINT’, EVERY THIRD MONTH. A HIGH PARTICLE AMOUNT COULD INDICATE
ABNORMAL WEAR AND THE TEAR IN THE SYSTEM, WHILE A LOW AMOUNT OF PARTICLES
REFLECTS A NORMAL CONDITION.
THE HYDRAULIC PUMPS ARE ALSO EQUIPPED WITH MAGNETIC CHIP DETECTORS LOCATED IN THE PUMP’S
DRAIN LINE .IF A BEARING FAILURE OCCURS, THIS WILL START THE PRODUCTION OF
MAGNETIC DEBRIS. THIS WILL STICK ON THE PARTICULAR PUMP’S MAGNET EQUIPPED WITH
AN ELECTRICAL SWITCH TRIGGING THE ALARM ‘EXCESSIVE WEAR’. IF THE ALARM IS
REPEATED JUST A FEW MINUTES AFTER CLEANING THE MAGNET,THE HYDRAULIC PUMPS MUST
BE OVERHAULED AND THE NECESSARY PARTS RENEWED.
FRAMO PRESSURE CONTROL SYSTEM ( A4V DP )
1. SYSTEM PRESSURE CONTROL
BLOCK: THE MAIN FUNCTION OF THE SYSTEM PRESSURE CONTROL BLOCK IS TO REGULATE
PILOT PRESSURE TO THE A4V PUMP
REGULATOR.PILOT PRESSURE IS CONTROLLED BY A COMMON SYSTEM PRESSURE CONTROL
VALVE.
2. UNLOADING VALVE
3. SYSTEM PRESSURE RELIEF
VALVE
4. SYSTEM PRESSURE CONTROL VALVE
5. PILOT CHECK VALVES
6. STRAINER: THE STRAINER IS
ONLY A LAST CHANCE PROTECTION, AND IS NOT LIKELY TO BE CLOGGED. SERVICE IS ONLY
NECESSARYWHEN TROUBLESHOOTING INDICATES CLOGGED STRAINER
THRUSTER CONTROL SYSTEM ( DSTC – 60 )
THRUSTER MOTOR
THRUSTER CONTROL VALVE: THE DSTC ( DIRECTIONAL
SPEED TORQUE CONTROLLER ) REGULATES THE TORQUE ( SPEED FROM ZERO TO MAXIMUM )
OF A FIXED PROPELLER IN BOTH DIRECTIONS ( PORT AND STARBOARD )THE HYDRAULIC
CONTROL VALVE, ( DSTC ) IS REMOTELY OPERATED FROM A BRIDGE OR WING CONTROL
PANEL. ELECTRIC / HYDRAULIC PILOT CONTROL BLOCK
THRUSTER PILOT CONTROL
ASSSEMBLY
THE PILOT CONTROL BLOCK IS
DESIGNED FOR REGULATING TWO PILOT PRESSURES ( PORT A AND B ) TO THE HYDRAULIC
CONTROL VALVE ( DSTC ).
DIRECTIONAL SPEED TORQUE
CONTROLLER , DSTC
THE HYDRAULIC CONTROL VALVE ,
DSTC -60-M CONSIST OF THE FOLLOWING MAIN PARTS :
TWO MANIFOLD MOUNTED SPEED
TORQUE CONTROLLER ( STC- 60 – M ), SIMILAR TO THE HYDRAULIC CONTROL VALVES FOR
THE FRAMO CARGO PUMPS .
ONE MANIFOLD
ONE HYDRAULIC PILOT CONTROL
BLOCK , MOUNTED ON THE MANIFOLD,
FILTER OF THE PILOT CONTROL BLOCK
BRIDGE AND WINGS PANELS
PROGRAMMABLE LOGIC CONTROL SPEED SENSOR
COUPLING REQUIREMENT: THE COUPLING BETWEEN THE HYDRAULIC MOTOR AND THE THRUSTER
MUST BE BALANCED IN ACCORDANCE WITH ISO - 1940/1 CLASS G6,3 AT MAXIMUM SPEED.
HYD. BRAKE PROTECTION: THE BRAKE WORKS BOTH WHEN THE THRUSTER IS IN OFF AND
STAND BY MODE
SERVICE INTERVALS OF THRUSTER CONTROL SYSTEM
--- THE PILOT FILTER SHOULD
BE CHECKED AT REGULAR INTERVALS .
--- CHECK THE VISUAL INDICATOR
WHEN THE SYSTEM IS WORKING AT NORMAL FLOW AND OPERATING TEMPERATURES.AS THE
ELEMENT GETS DIRTY RED WILL APPEAR IN THE WINDOW. AT THIS POINT , PRIOR TO THE
OPENING OF THE BY-PASS VALVE , THE ELEMENT SHOULD BE CHANGED.THE FILTER ELEMENT
IS NOT CLEANABLE.
--- THE LAST CHANCE FILTERS
INSIDE THE DSTC SHOULD BE REPLACED IF CLOGGED
--- THE DEBRIS DETECTOR ,
WHICH IS INCLUDED IN THE NON RETURN VALVE IN THE MOTOR RETURN LINE, MUST BE
CHECKED MANUALLY.
Hiç yorum yok:
Yorum Gönder